Ring Circuit Fault Finding Plus Green Goo

2024 ж. 13 Мам.
18 533 Рет қаралды

UK electrician Matt is fault finding on a ring final circuit. The socket circuit is tripping the RCCB inside of the split load consumer unit. Matts identifies the faulty ring circuit and then uses a logical approach to find the part of the ring that has an earth fault on it. By splitting the ring apart Matt creates a radial socket circuit and then sets about getting as many socket on as possible. It is also interesting to see how this older PVC is staring to break down creating green goo around the outlets.
🔔 Subscribe for more free electrical training videos kzhead.info?s...
== 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - Fault on the socket circuit
00:23 - Found the faulty circuit
01:26 - Identifying the faulty leg
02:13 - Splitting the circuit
04:49 - Green goo
05:10 - Consumer unit connections
06:34 - 3 phase supply
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical”.
▶️ FACEBOOK / gshelectrical
▶️ INSTAGRAM / brihzmraygdtmjmdb9lunq...
▶️ TWITTER / gsh_electrical
▶️ TikTok vm.tiktok.com/ZMRBLFdhe/
#GSHElectrical #Electricaltrainingvideos #electricaltesting #faultfinding #electricalwiring #greegoo #eectrical

Пікірлер
  • The green goo is the plasticiser coming out of the insulation. Currently all manufacturers are saying no need to rush and rewire BUT the green goo is a HSE risk so wearing gloves is appropriate NOT to get Di-isoctyl phthalate on your skin. I have seen cables insulation become brittle with cracking so needs monitoring! 5:08

    @Electronics-Rocks@Electronics-Rocks Жыл бұрын
    • Thanks Shaun for taking the time to watch and comment

      @GSHElectrical@GSHElectrical Жыл бұрын
  • Well done Matt I can’t remember ever seeing the green goo , to me i think it help to age the installation along with the fact that the conductors are stranded, so I think it dates back to the late thifteys late sixties. Also who would have guessed that guy gaz interviewed is your dad . Great video as always Matt 👍

    @Dog-whisperer7494@Dog-whisperer7494 Жыл бұрын
    • 1965 if his estimate of how old his dad was when he wired it are correct

      @andrewjames3908@andrewjames39085 ай бұрын
  • Isn’t the box above the Consumer unit a relocation box? Looks on the footage that the old cables go to that, then new colours from that to CU.

    @OverlandSea@OverlandSea Жыл бұрын
  • There doesn’t seem to be much information about the green goo in general. In fact unless you have seen it you probably wouldn’t believe it. On one job it was so bad it was running down the walls. Last year I part rewired a bungalow. The customer didn’t know what I was on about until I showed them a couple joint boxes from the loft full of the goo.

    @andysims4906@andysims4906 Жыл бұрын
  • If you haven't seen the green goo it's just like fairy liquid . It's a breakdown of the insulation, doesn't mean it's been overloaded necessarily. I have seen it on lighting circuits more than sockets . Sometimes it's an odd piece of cable I a whole house . Definitely 1970s houses which can suffer from the problem. Lots of houses are rewired before if becomes an issue because people move house and renovate etc , we have more electrical appliances than ever so need more sockets hence houses are rewired .

    @dennisphoenix1@dennisphoenix1 Жыл бұрын
    • Seems like it would mostly happen in places where the wires are coming down from above. So any length of wire above the guy could build up and leak down the length of the cable over time and come out the end. Since most socket writing now it's from the floor up and is from the ceiling down it's going to happen more on lighting rings and in bungalows maybe where the mains trying is wired in the roof down.... Maybe.

      @ge2719@ge2719 Жыл бұрын
    • @@ge2719 that would make sense. Gravity

      @dennisphoenix1@dennisphoenix1 Жыл бұрын
    • I've had it on an extension lead, coming out of the trailing socket. Proper old stuff, non-earthed German plug and twin flex, moulded plug and trailing socket, 50s or early 60s probably. The whole thing had a peculiar chemical smell to it so the process might well have something to do with plasticisers reacting with the copper.

      @Ragnar8504@Ragnar8504 Жыл бұрын
  • Avoid touching it with bare fingers. Its like a fine oil that gets into your skin. It doesn't wash off instantly and can make your eyes sting if they come into contact with your hands...Even if you've washed them and they are bone dry. It also gives of a distinctive smell, I cant describe it but once you've smelt it once, you wont forget it.

    @aj285@aj285 Жыл бұрын
  • 100 acre estate Hoddesdon has the green goo, also has stainless steel tube on plumbing. Dates it early’70s when there were copper shortages because of war in Rhodesia.

    @camwinstone@camwinstone11 ай бұрын
  • Not seen electrical go full goo myself but I have seen the precursors where the insulation on a core has started to react with the copper, beginning to chew it up and also stuck to it making it difficult to pull off.

    @retrozmachine1189@retrozmachine1189 Жыл бұрын
  • Hi. I have my 10 hours Bay assesment tommorow. Do you have any good advise for it since im prepared but nervous

    @mohammedobad5219@mohammedobad521911 ай бұрын
  • that's a rewire all day long, so many sparks want the quick money of consumer units.

    @davidwhitefoot5680@davidwhitefoot5680 Жыл бұрын
  • Property sounds like it needs an Electrician and The Ghostbusters.

    @mavez6322@mavez6322 Жыл бұрын
    • Great point 😀

      @GSHElectrical@GSHElectrical Жыл бұрын
  • Artisan Electrics had a video once where an installation had the green goo appearing

    @leeroberts1192@leeroberts1192 Жыл бұрын
  • How to find Electrical fault in house wiring circuit

    @muhammadashfaq4419@muhammadashfaq44198 ай бұрын
  • Only ever had it on lighting circuits to date, never on a socket.

    @PHealey1981@PHealey1981 Жыл бұрын
    • 👍🏻

      @GSHElectrical@GSHElectrical Жыл бұрын
  • All the 6 amp lighting circuits on one Rcd Rccb and a din rail Doorbell transformer in a plastic non amendment 3 2015 enclosure Fab.

    @danvictor3934@danvictor3934 Жыл бұрын
    • 421.1.201 Within domestic (household) premises, consumer units and similar switchgear assemblies shall comply with BS EN 61439-3 and shall: (i) have their enclosure manufactured from non-combustible material, or (ii) be enclosed in a cabinet or enclosure constructed of non-combustible material and complying with Regulation 132.12. Not sure the Transformer would qualify as switchgear.

      @conarobrien9434@conarobrien9434 Жыл бұрын
    • @@conarobrien9434 Problem is similar switch gear assembly is open to wild interpretation depending on the person.

      @danvictor3934@danvictor3934 Жыл бұрын
    • @@danvictor3934 While I generally agree that it is open to far more interpretation than it should be, in the specific case of a doorbell transformer I don't think it could be argued that it counts as switchgear. Switchgear is defined as: "An assembly of main and auxiliary switching equipment for operation, regulation and protection or other control of an electrical installation." eFIXX did a video on the subject about a month ago, covering the related regulations: "The WAGO Junction Box Debate: Metal or Plastic?"

      @yngndrw.@yngndrw.11 ай бұрын
    • The two lighting circuits on the same RCD is probably because of a borrowed neutral. That's common on older installations. It's a workaround, but the alternative is very disruptive. In this case it looks like the householder is facing having to pay for a rewire anyway with the cable insulation breaking down.

      @TheEulerID@TheEulerID9 ай бұрын
  • There was green goo coming out of the junction box over the CU. He did not look inside.

    @johnburns4017@johnburns4017 Жыл бұрын
  • So what is the green goo?

    @SmithyScotland@SmithyScotland Жыл бұрын
    • Verdigris.

      @mastergraphic9998@mastergraphic9998 Жыл бұрын
    • Poor quality cable insulation breaks down and reacts with the copper

      @mastergraphic9998@mastergraphic9998 Жыл бұрын
  • You might benefit from having multiple cameras.

    @JingleBaza@JingleBaza Жыл бұрын
    • Sadly Matt was on his own 👍🏻

      @GSHElectrical@GSHElectrical Жыл бұрын
  • Rings are in the road , finals are in the house!

    @oc7414@oc7414 Жыл бұрын
    • He never said main so what's the problem old school knows what he meant

      @dav01kar@dav01kar Жыл бұрын
  • Where was the fault?

    @johnburns4017@johnburns4017 Жыл бұрын
  • 1.4 ohms on each leg of the ring? That ring main is too long.

    @Spark101.@Spark101. Жыл бұрын
  • So basically you didn't find the fault.

    @DJMaverickk@DJMaverickk10 ай бұрын
    • Not in this video

      @GSHElectrical@GSHElectrical10 ай бұрын
  • Presumably the wires are overheating because there's a huge amount of resistance somewhere in that ring, right? It's not overheating because the customer is running too much current through it. (I only passed my L3 qual this year, hence the simpleton question).

    @syncopatedsteve@syncopatedsteve Жыл бұрын
    • It might just be the age of the wires. 50+ years old, those bright red wires might have been new tech that just turned out to not be that great over time. Like how products now that have a thin rubber coating like console controllers, can end up going all sticky from the rubber failing over time. The new modern twin core with brown wire probably has a better coating that doesn't turn into goo 😂

      @ge2719@ge2719 Жыл бұрын
    • That green goo, shorting on a contact i bet if you put all the sockets in wagos and retest the IR would be clear

      @ericthekingthekingtheking4842@ericthekingthekingtheking4842 Жыл бұрын
    • It is not wires overheating. It is the breakdown of plastciser in 1960's 70's cable. Over time it will show on the insulation test as it does in this video. The same pesticides was also very tasty for rats and mice. Insulation tests between each of the sockets which have been isolated an hour pd the consumer unit will pin down the area of the fault. I would have checked the box where all the red/black cables have been extended by Brown/blue cable as a matter of urgency as there was green goo running out of the box. Green goo is an indicator of electrical insulation breaking down and is confirmed by the low resistance in the insulation test.

      @kennethdavidson9564@kennethdavidson9564 Жыл бұрын