Cable calculation. Calculating the live cable size from BS 7671

2023 ж. 18 Қаз.
6 095 Рет қаралды

This video is mainly aimed at students on Level 3 and Apprentices. The video shows a step by step method how to calculate the size on the live cable only using BS 7671. Each formula you need is shown and explained, each table used and page is shown in detail.
Finding Ib, In, It, Iz and all relevant C factors. Finding the reference methods, mV/A/m value and calculating volt drop.

Пікірлер
  • You are a legend, best video on cable calcs hands down.

    @ashleyhutton7046@ashleyhutton7046Ай бұрын
    • @@SpinSkins Would you know the formula on how to work out the Iz of a 4mm ring circuit?

      @ashleyhutton7046@ashleyhutton704625 күн бұрын
    • Thank you mate, glad my videos help you

      @ElectricalStudentsUK@ElectricalStudentsUK25 күн бұрын
  • Well done,excellent and clear explanation, may God bless you ,thanks

    @HH-oi8hn@HH-oi8hn26 күн бұрын
    • Thank you, I hope my explanations help with your learning journey

      @SpinSkins@SpinSkins26 күн бұрын
    • @@SpinSkins your explanation really helped me understand some things that were Ambiguous to me. Thanks 🙏

      @HH-oi8hn@HH-oi8hn26 күн бұрын
  • Thanks for this video, I’ve just studied this but couldn’t get my head around it.

    @lukehobson9003@lukehobson90036 ай бұрын
  • Could you please do a video on the tabs you’ve got on your regs book, looks so much easier to navigate. 🙏

    @nickbanwell5771@nickbanwell57713 ай бұрын
  • Your handwriting beautiful

    @HH-oi8hn@HH-oi8hn26 күн бұрын
  • Glad it has helped you. For an indepth, step by step, page by page guide, check out the shop www.electricalstudent.co.uk

    @ElectricalStudentsUK@ElectricalStudentsUK6 ай бұрын
  • Minutes 13, should be written mV/A/M.

    @eyazdani4537@eyazdani45373 ай бұрын
    • Yes well spotted! Sorry for my mistake

      @ElectricalStudentsUK@ElectricalStudentsUK3 ай бұрын
    • Thanks for your informative educational videos. 👍

      @eyazdani4537@eyazdani45373 ай бұрын
    • No worries mate. Anything you're unsure of and want me to go over for you, let me know

      @ElectricalStudentsUK@ElectricalStudentsUK3 ай бұрын
  • At 19.27 you choose to put “In” on top of the equation. In this example, surely “Ib” can be used, as this is a fixed load (water heater), that cannot be overloaded?

    @gbelectricks@gbelectricks6 ай бұрын
    • In short, no. Page 167 of the OSG gives you the equation of It>In divided by the C factors. Also Regulation 433.1.1 details how the In must nit exceed the Iz value. Which is found by In divided by the C factors

      @ElectricalStudentsUK@ElectricalStudentsUK6 ай бұрын
    • @@ElectricalStudentsUK that might be ok in a class room, but your way is wasteful in a real install. you only use In for your CCC if you can overload the circuit. 433.1.1 says that your In must be less than It & it will be regardless of which one you use. The OSG is limited in most of its explanations because of the regs so it’s not written in stone that you have to use In.😂

      @goaway9487@goaway9487Ай бұрын
  • Great video. Starting my lvl 3 next week

    @sasalotas@sasalotas3 ай бұрын
    • This video will really help you, check out my level 3 formula videos when you start the maths and scientific principles module. There are formula sheets and a step by step cable calculations guide in my shop at www.electricalstudent.co.uk They will be really helpful to you

      @ElectricalStudentsUK@ElectricalStudentsUK3 ай бұрын
  • You should be using Your design current as this circuit can’t be overloaded. 433.1.1 says you can as long as it’s a greater value than both design & protective device rating currents. Using your way is not very practical in the real world & leads to larger & more expensive cables when they’re not really needed.

    @goaway9487@goaway9487Ай бұрын
KZhead